Product Description
PRNT High voltage current limiting fuse for overload protection of oil-immersed transformers is suitable for 50 Hz AC systems with Rated voltage of 15.5 kV and 40.5 kV, and is used inside transformer oil to protect American‑style power transformers and other electrical equipment against overloads and minor fault short-circuit currents. This product must not be used alone; it must be connected in series with the XRNT4 High voltage current limiting fuse for backup protection of oil-immersed transformers to provide comprehensive protection for the transformer.
Model number

Basic Parameters

Appearance and Installation Dimensions


Installation Steps
1. Open the latch on the handle and pull the handle out of the base.
2. Use a wrench to loosen the screw tube in the handle and the end bolt.
3. Loosen the screw tube and the end screw bolt;
4. Insert the fuse-link into the screw tube;
5. The flared cap of the fuse-link must be positioned between the screw and the handle;
6. Secure the handle with a wrench, applying a torque of approximately 5.6–7.9 N·m.
7. Unfold the funnel-shaped cap;
8. Use one wrench to hold the bolt at the end of the screw tube, and use another wrench to tighten the opposite-end bolt to a torque of approximately 5.6–7.9 N·m.
9. Insert the handle into the base, turn the handle’s latch to secure the fuse.
The PRNT4-type overload fuse and the XRNT4-type backup current-limiting fuse can be selected according to the table below.