High voltage current limiting fuse for backup protection of oil-immersed transformers
Overview:
Keywords:
Fuse
Category:
High-voltage fuse
Product Description
The XRNT4 oil-immersed transformer backup protection high voltage current-limiting fuse is suitable for indoor high-voltage systems with an AC frequency of 50 Hz, a Rated voltage of 10–40.5 kV, and a Rated current of 20 A–315 A. It serves as short-circuit protection for power transformers and can be used in series with the PRNT4 oil-immersed transformer overload protection high-voltage fuse to provide comprehensive protection for the transformer. This product is a dedicated backup high-voltage current-limiting fuse for American-style pad-mounted substations.
Model Meaning

Basic Parameters

Appearance and Installation Dimensions

Characteristic coordination curve of the back-up fuse and the overload fuse
The overload fuse must not be used alone; it must be connected in series with the back-up fuse. When selecting these components, full consideration should be given to the protective characteristics of both the overload fuse and the back-up fuse. 
The figure on the right shows the characteristic curves of the two devices, where A is the intersection point of the two curves, B is the minimum breaking current of the back-up fuse, and C is the maximum breaking current of the overload fuse.
When using it, first, point A must exist and its value should be less than the rated breaking capacity of the overload fuse; second, point B must be above point A, and point C must be below point A.
Related Products